Supports 208V/480V grid voltage, 100% unbalanced loads, 4 MPPTs with up to 90kW PV input, dual 80A battery ports compatible with 314Ah cells, and built-in RSD transmitter.
Compatible with both 208V and 480V North American standard grid architectures, reducing site adaptation costs
Built-in RSD transmitter simplifies compliance and safety installation requirements
High PV input power capability (up to 90kW) maximizes solar energy harvesting
Reduce dependence on fossil fuels and achieve cleaner, lower-carbon C&I energy management
Maximize PV self-consumption and increase the penetration of renewable energy

| Model | R36KH3NA 208V | R60KH3NA 480V |
| Battery data | ||
| Max. charging / discharging power (kW) | 36 | 60 |
| Battery voltage range (V) | 150~500 | 150~800 |
| Max. charging / discharging current(A) | 80*2 | |
| No. of battery input | 2 | |
| Battery type | Lithium-ion | |
| PV input data | ||
| Max. PV access power (kW) | 54 | 90 |
| Max. PV input power (kW) | 54 | 90 |
| Max. PV voltage (V) | 600 | 1000 |
| MPPT voltage range (V) | 150~550 | 150~850 |
| Start-up voltage (V) | 180 | |
| Max. input current per MPPT (A) | 40 / 40 / 40 / 40 | |
| Max. short-circuit current (A) | 50 / 50 / 50 / 50 | |
| No. of MPPT trackers | 4 | |
| No. of PV strings per MPPT | 2 | |
| Rated input voltage (V) | 400 | 600 |
| AC output data (on-grid) | ||
| Rated AC output power (kW) | 36 | 60 |
| Rated AC output current (A) | 100 | 72 |
| Max. continuous AC pass-through(grid to load) (A) | 200 | |
| Rated grid voltage (V) | 208 | 480 |
| Grid type | 3W+N+PE | |
| Rated grid frequency (Hz) | 50 / 60 | |
| THDi | <3% | |
| AC output data (off-grid) | ||
| Rated output power (kW) | 36 | 60 |
| Rated output voltage (V) | 208(3W+N+PE) | 480(3W+N+PE) |
| Rated output current(A) | 100 | 72 |
| Back-up switch time (ms) | <10 | |
| Rated frequency(Hz) | 60 | |
| THDu | <2% | |
| Protection | ||
| Island protection | Supported | |
| PV reverse polarity protection | Supported | |
| Battery reverse polarity protection | Supported | |
| Insulation monitoring | Supported | |
| Residual current monitoring | Supported | |
| AC over current protection | Supported | |
| AC over power protection | Supported | |
| Back-up output short protection | Supported | |
| Short circuit protection | Supported | |
| RSD transimitter | Supported | |
| Display and communication | ||
| HMI | APP; touch panel | |
| BMS | RS485,CAN | |
| EMS | RS485 | |
| Meter | RS485 | |
| Supported communication interface | WIFI or 4G or GPRS | |
| General data | ||
| Dimensions W*D*H (mm) | 530*280*850 | |
| Weight (kg) | 73 | |
| Ingress protection | IP65 | |
| Operating temperature range (℃) | -30~60 | |
| Inverter topology | Non-isolated | |
| Relative humidity | 0~100% | |
| Operating altitude (m) | 4,000(>2,000 power derating) | |
| Cooling | Forced air cooling | |
| Noise emission (dB) | ≤65 | |
| Installation | Wall mounted type | |