Save more installation, commissioning costs
Reduce the use of fossil fuels and be more environmentally friendly
Increase the penetration of renewable energy
Continuous and stable power supply
Avoid the upgrading of grid and achieve the expected effect quickly
| Rated power (kW) | 2,400 | 2,750 | 3,150 | 2,500 | 3,450 |
| DC data | |||||
| DC voltage range (V) | 696~1,500 | 800~1,500 | 920~1,500 | 1,000~1,500 | 1,000~1,500 |
| Max. DC current (A) | 1,935*2 | 1,402*2 | 1,935*2 | ||
| Number of DC input circuits | 2 | ||||
| AC data | |||||
| Rated power (kW) | 2,400 | 2,750 | 3,150 | 2,500 | 3,450 |
| Max. output power (kW) | 2,640 | 3,025 | 3,465 | 2,750 | 3,795 |
| Reactive power range (kvar) | 0~2,520 | 0~2,888 | 0~3,308 | 0~2,625 | 0~3,623 |
| Rated AC current (A) | 2,886 | 2,092 | 2,886 | ||
| Grid type | 3W+PE | ||||
| Isolation method | No isolation | ||||
| Grid-connected operation data | |||||
| Rated grid frequency (Hz) | 50 / 60 | ||||
| Total harmonic distortion of current | <3% (Rated power) | ||||
| Power factor | -1~1 | ||||
| Charge-discharge conversion time (ms) | <30 | ||||
| Voltage regulation accuracy | ±1% | ||||
| Current stability accuracy | ±2% | ||||
| Off-grid operation data | |||||
| Rated output voltage (V) | 480 | 550 | 630 | 690 | 690 |
| Voltage imbalance | 2%, not exceeding 4% for short periods | ||||
| THDu | <3%(No load or rated resistive load) | ||||
| Dynamic voltage transient range | 10% (under resistive load/balanced load conditions, when the load suddenly changes from 20% to 100% or from 100% to 20%) | ||||
| Output overvoltage protection value | Adjustable | ||||
| Output undervoltage protection value | Adjustable | ||||
| General data | |||||
| Applicable grounding system | IT | ||||
| Max. efficiency | 99.01% | ||||
| Allowable ambient temperature (℃) | -40~+60 (Use with derating above 45) | ||||
| Allowable relative humidity | 0~100%(No condensation) | ||||
| Allowable altitude (m) | <5,000 (A reduction of over 3,000) | ||||
| Noise (dB) | 75 | ||||
| DI interface | Group 4 | ||||
| DO interface | Group 1 | ||||
| Corrosion resistance grade | C3 (C4 / C5 optional) | ||||
| Overvoltage protection | DC Type ІІ / AC Type ІІІ | ||||
| Wiring method | Bottom-in-bottom-out | ||||
| Protection grade | IP66 | ||||
| Cooling method | Intelligent heat exchange | ||||
| Indicator light | Touch screen | ||||
| Communication interface | Ethernet, RS485 | ||||
| Communication protocol | Modbus TCP / RTU,IEC61850,IEC104 | ||||
| Dimensions (W*H*D) (mm) | 1,700*2,633*1,319 (with radiator) | ||||
| Weight (kg) | ≤2,300 | ||||
| Certification | CGC, high/low voltage ride-through | ||||